Design Column Strength, Tied Columns
Structural Design · FE Reference Handbook section
Handbook notes for this section
Definitions and conditions exactly as the handbook states them.
- Nominal Column Strength Interaction Diagram for Rectangular Section
Core formulas for this FE topic
Definitions, applicability, units, assumptions and worked examples for each relation.
Worked exam-style examples
The four ways this section is written on the real exam — thoughts first, then equations, then substitution.
A square tied column in a parking structure is sized using design column strength, tied columns provisions. Given resistance factor (phi) = 0.6400; concrete strength (f_c) = 3.2000 ksi; gross column area (A_g) = 325.0 in^2; steel reinforcement area (A_st) = 23.0000 in^2; steel yield strength (f_y) = 61.0000 ksi, determine the design strength of tied column (P_n_phi) in kip.
Given
Find
design strength of tied column (P_n_phi), in kip
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except P_n_phi is given, so isolate P_n_phi symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 1 — schematic for Design strength of tied columns — solve for design strength of tied column — Design Column Strength, Tied Columns
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for P_n_phi:
Step 3 — List the givens: resistance factor (phi) = 0.6400, concrete strength (f_c) = 3.2000 ksi, gross column area (A_g) = 325.0 in^2, steel reinforcement area (A_st) = 23.0000 in^2, steel yield strength (f_y) = 61.0000 ksi.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Step 6 — Check: returning P_n_phi = 1,139 kip to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 2,278 — kept a factor of two that cancels in the correct rearrangement.
- 569.5 — dropped that same factor in the other direction.
- 1,253 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
An interior building column's design column strength, tied columns capacity is checked against factored axial load. Given resistance factor (phi) = 0.6000; concrete strength (f_c) = 3.9000 ksi; steel reinforcement area (A_st) = 2.0000 in^2; steel yield strength (f_y) = 59.0000 ksi; design strength of tied column (P_n_phi) = 791.0 kip, determine the gross column area (A_g) in in^2.
Given
design strength of tied column (P_n_phi) = 791.0 kip
Find
gross column area (A_g), in in^2
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except A_g is given, so isolate A_g symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 2 — schematic for Design strength of tied columns — solve for gross column area — Design Column Strength, Tied Columns (2)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for A_g:
Step 3 — List the givens: resistance factor (phi) = 0.6000, concrete strength (f_c) = 3.9000 ksi, steel reinforcement area (A_st) = 2.0000 in^2, steel yield strength (f_y) = 59.0000 ksi, design strength of tied column (P_n_phi) = 791.0 kip.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
A_{g} = 465.5\ \text{in^2}Step 6 — Check: returning A_g = 465.5 in^2 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 931.0 — kept a factor of two that cancels in the correct rearrangement.
- 232.8 — dropped that same factor in the other direction.
- 512.1 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A tied column supporting a mezzanine is evaluated for design column strength, tied columns. Given resistance factor (phi) = 0.6200; concrete strength (f_c) = 3.6000 ksi; gross column area (A_g) = 200.0 in^2; steel reinforcement area (A_st) = 22.0000 in^2; steel yield strength (f_y) = 67.0000 ksi, determine the design strength of tied column (P_n_phi) in kip.
Given
Find
design strength of tied column (P_n_phi), in kip
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except P_n_phi is given, so isolate P_n_phi symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 3 — schematic for Design strength of tied columns — solve for design strength of tied column (case 2) — Design Column Strength, Tied Columns (3)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for P_n_phi:
Step 3 — List the givens: resistance factor (phi) = 0.6200, concrete strength (f_c) = 3.6000 ksi, gross column area (A_g) = 200.0 in^2, steel reinforcement area (A_st) = 22.0000 in^2, steel yield strength (f_y) = 67.0000 ksi.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Step 6 — Check: returning P_n_phi = 1,001 kip to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 2,003 — kept a factor of two that cancels in the correct rearrangement.
- 500.6 — dropped that same factor in the other direction.
- 1,101 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A square tied column in a parking structure is sized using design column strength, tied columns provisions. Given resistance factor (phi) = 0.6400; concrete strength (f_c) = 3.7000 ksi; steel reinforcement area (A_st) = 3.5000 in^2; steel yield strength (f_y) = 43.0000 ksi; design strength of tied column (P_n_phi) = 553.0 kip, determine the gross column area (A_g) in in^2.
Given
design strength of tied column (P_n_phi) = 553.0 kip
Find
gross column area (A_g), in in^2
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except A_g is given, so isolate A_g symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 4 — schematic for Design strength of tied columns — solve for gross column area (case 2) — Design Column Strength, Tied Columns (4)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for A_g:
Step 3 — List the givens: resistance factor (phi) = 0.6400, concrete strength (f_c) = 3.7000 ksi, steel reinforcement area (A_st) = 3.5000 in^2, steel yield strength (f_y) = 43.0000 ksi, design strength of tied column (P_n_phi) = 553.0 kip.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
A_{g} = 302.6\ \text{in^2}Step 6 — Check: returning A_g = 302.6 in^2 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 605.1 — kept a factor of two that cancels in the correct rearrangement.
- 151.3 — dropped that same factor in the other direction.
- 332.8 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
An interior building column's design column strength, tied columns capacity is checked against factored axial load. Given resistance factor (phi) = 0.6200; concrete strength (f_c) = 4.2000 ksi; gross column area (A_g) = 205.0 in^2; steel reinforcement area (A_st) = 18.0000 in^2; steel yield strength (f_y) = 50.0000 ksi, determine the design strength of tied column (P_n_phi) in kip.
Given
Find
design strength of tied column (P_n_phi), in kip
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except P_n_phi is given, so isolate P_n_phi symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 5 — schematic for Design strength of tied columns — solve for design strength of tied column (case 3) — Design Column Strength, Tied Columns (5)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for P_n_phi:
Step 3 — List the givens: resistance factor (phi) = 0.6200, concrete strength (f_c) = 4.2000 ksi, gross column area (A_g) = 205.0 in^2, steel reinforcement area (A_st) = 18.0000 in^2, steel yield strength (f_y) = 50.0000 ksi.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Step 6 — Check: returning P_n_phi = 777.5 kip to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 1,555 — kept a factor of two that cancels in the correct rearrangement.
- 388.8 — dropped that same factor in the other direction.
- 855.3 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A tied column supporting a mezzanine is evaluated for design column strength, tied columns. Given resistance factor (phi) = 0.6500; concrete strength (f_c) = 5.5000 ksi; steel reinforcement area (A_st) = 21.0000 in^2; steel yield strength (f_y) = 53.0000 ksi; design strength of tied column (P_n_phi) = 328.0 kip, determine the gross column area (A_g) in in^2.
Given
design strength of tied column (P_n_phi) = 328.0 kip
Find
gross column area (A_g), in in^2
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except A_g is given, so isolate A_g symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 6 — schematic for Design strength of tied columns — solve for gross column area (case 3) — Design Column Strength, Tied Columns (6)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for A_g:
Step 3 — List the givens: resistance factor (phi) = 0.6500, concrete strength (f_c) = 5.5000 ksi, steel reinforcement area (A_st) = 21.0000 in^2, steel yield strength (f_y) = 53.0000 ksi, design strength of tied column (P_n_phi) = 328.0 kip.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
A_{g} = -61.1510\ \text{in^2}Step 6 — Check: returning A_g = -61.1510 in^2 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- -122.3 — kept a factor of two that cancels in the correct rearrangement.
- -30.5755 — dropped that same factor in the other direction.
- -67.2661 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A square tied column in a parking structure is sized using design column strength, tied columns provisions. Given resistance factor (phi) = 0.6100; concrete strength (f_c) = 4.9000 ksi; gross column area (A_g) = 300.0 in^2; steel reinforcement area (A_st) = 2.0000 in^2; steel yield strength (f_y) = 71.0000 ksi, determine the design strength of tied column (P_n_phi) in kip.
Given
Find
design strength of tied column (P_n_phi), in kip
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except P_n_phi is given, so isolate P_n_phi symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 7 — schematic for Design strength of tied columns — solve for design strength of tied column (case 4) — Design Column Strength, Tied Columns (7)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for P_n_phi:
Step 3 — List the givens: resistance factor (phi) = 0.6100, concrete strength (f_c) = 4.9000 ksi, gross column area (A_g) = 300.0 in^2, steel reinforcement area (A_st) = 2.0000 in^2, steel yield strength (f_y) = 71.0000 ksi.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Step 6 — Check: returning P_n_phi = 675.0 kip to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 1,350 — kept a factor of two that cancels in the correct rearrangement.
- 337.5 — dropped that same factor in the other direction.
- 742.5 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
An interior building column's design column strength, tied columns capacity is checked against factored axial load. Given resistance factor (phi) = 0.6200; concrete strength (f_c) = 6.0000 ksi; steel reinforcement area (A_st) = 6.5000 in^2; steel yield strength (f_y) = 67.0000 ksi; design strength of tied column (P_n_phi) = 2,120 kip, determine the gross column area (A_g) in in^2.
Given
design strength of tied column (P_n_phi) = 2,120 kip
Find
gross column area (A_g), in in^2
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except A_g is given, so isolate A_g symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 8 — schematic for Design strength of tied columns — solve for gross column area (case 4) — Design Column Strength, Tied Columns (8)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for A_g:
Step 3 — List the givens: resistance factor (phi) = 0.6200, concrete strength (f_c) = 6.0000 ksi, steel reinforcement area (A_st) = 6.5000 in^2, steel yield strength (f_y) = 67.0000 ksi, design strength of tied column (P_n_phi) = 2,120 kip.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
A_{g} = 765.7\ \text{in^2}Step 6 — Check: returning A_g = 765.7 in^2 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 1,531 — kept a factor of two that cancels in the correct rearrangement.
- 382.8 — dropped that same factor in the other direction.
- 842.3 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A tied column supporting a mezzanine is evaluated for design column strength, tied columns. Given resistance factor (phi) = 0.6000; concrete strength (f_c) = 3.8000 ksi; gross column area (A_g) = 555.0 in^2; steel reinforcement area (A_st) = 3.0000 in^2; steel yield strength (f_y) = 73.0000 ksi, determine the design strength of tied column (P_n_phi) in kip.
Given
Find
design strength of tied column (P_n_phi), in kip
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except P_n_phi is given, so isolate P_n_phi symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 9 — schematic for Design strength of tied columns — solve for design strength of tied column (case 5) — Design Column Strength, Tied Columns (9)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for P_n_phi:
Step 3 — List the givens: resistance factor (phi) = 0.6000, concrete strength (f_c) = 3.8000 ksi, gross column area (A_g) = 555.0 in^2, steel reinforcement area (A_st) = 3.0000 in^2, steel yield strength (f_y) = 73.0000 ksi.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Step 6 — Check: returning P_n_phi = 960.9 kip to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 1,922 — kept a factor of two that cancels in the correct rearrangement.
- 480.5 — dropped that same factor in the other direction.
- 1,057 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns
A square tied column in a parking structure is sized using design column strength, tied columns provisions. Given resistance factor (phi) = 0.6500; concrete strength (f_c) = 3.8000 ksi; steel reinforcement area (A_st) = 22.5000 in^2; steel yield strength (f_y) = 43.0000 ksi; design strength of tied column (P_n_phi) = 2,773 kip, determine the gross column area (A_g) in in^2.
Given
design strength of tied column (P_n_phi) = 2,773 kip
Find
gross column area (A_g), in in^2
Start with the thinking
- The governing relation printed in this handbook section is Design strength of tied columns.
- Everything except A_g is given, so isolate A_g symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Design column strength, tied columns, combines the concrete and reinforcement contributions with a 0.80 reduction for accidental eccentricity.
Figure 10 — schematic for Design strength of tied columns — solve for gross column area (case 5) — Design Column Strength, Tied Columns (10)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for A_g:
Step 3 — List the givens: resistance factor (phi) = 0.6500, concrete strength (f_c) = 3.8000 ksi, steel reinforcement area (A_st) = 22.5000 in^2, steel yield strength (f_y) = 43.0000 ksi, design strength of tied column (P_n_phi) = 2,773 kip.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
A_{g} = 1396\ \text{in^2}Step 6 — Check: returning A_g = 1,396 in^2 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 2,793 — kept a factor of two that cancels in the correct rearrangement.
- 698.2 — dropped that same factor in the other direction.
- 1,536 — rounded an intermediate value before the final step.
Reference: FE Handbook — Structural Design: Design Column Strength, Tied Columns