Skip to content

Basic combinations

Structural Design · FE Reference Handbook section

Structural Design
2 formulas
10 exam-style examples
~49 min
All Structural Design lectures

Handbook notes for this section

Definitions and conditions exactly as the handbook states them.

  • Nominal loads used in the following combinations

Core formulas for this FE topic

Definitions, applicability, units, assumptions and worked examples for each relation.

Worked exam-style examples

The four ways this section is written on the real exam — thoughts first, then equations, then substitution.

Example 1
Governing LRFD (strength) load combination — Basic combinations

A floor system carries D = 48 psf, L = 80 psf and Lr = 22 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=48psfD = 48 psf
  • L=80psfL = 80 psf
  • Lr=22psfLr = 22 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(48)=67.2psf1.4D = 1.4(48) = 67.2 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(48)+1.6(80)+0.5(22)=196.6psf1.2D + 1.6L + 0.5Lr = 1.2(48) + 1.6(80) + 0.5(22) = 196.6 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(48)+1.6(22)+1.0(80)=172.8psf1.2D + 1.6Lr + 1.0L = 1.2(48) + 1.6(22) + 1.0(80) = 172.8 psf
  4. Compare — governing value is 196.6 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 196.6 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 150.0 psf (service loads added without factors)
  • 67.2 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 2
Governing LRFD (strength) load combination — Basic combinations (2)

A floor system carries D = 66 psf, L = 97 psf and Lr = 25 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=66psfD = 66 psf
  • L=97psfL = 97 psf
  • Lr=25psfLr = 25 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(66)=92.4psf1.4D = 1.4(66) = 92.4 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(66)+1.6(97)+0.5(25)=246.9psf1.2D + 1.6L + 0.5Lr = 1.2(66) + 1.6(97) + 0.5(25) = 246.9 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(66)+1.6(25)+1.0(97)=216.2psf1.2D + 1.6Lr + 1.0L = 1.2(66) + 1.6(25) + 1.0(97) = 216.2 psf
  4. Compare — governing value is 246.9 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 246.9 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 188.0 psf (service loads added without factors)
  • 92.4 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 3
Governing LRFD (strength) load combination — Basic combinations (3)

A floor system carries D = 78 psf, L = 64 psf and Lr = 21 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=78psfD = 78 psf
  • L=64psfL = 64 psf
  • Lr=21psfLr = 21 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(78)=109.2psf1.4D = 1.4(78) = 109.2 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(78)+1.6(64)+0.5(21)=206.5psf1.2D + 1.6L + 0.5Lr = 1.2(78) + 1.6(64) + 0.5(21) = 206.5 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(78)+1.6(21)+1.0(64)=191.2psf1.2D + 1.6Lr + 1.0L = 1.2(78) + 1.6(21) + 1.0(64) = 191.2 psf
  4. Compare — governing value is 206.5 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 206.5 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 163.0 psf (service loads added without factors)
  • 109.2 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 4
Governing LRFD (strength) load combination — Basic combinations (4)

A floor system carries D = 47 psf, L = 100 psf and Lr = 24 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=47psfD = 47 psf
  • L=100psfL = 100 psf
  • Lr=24psfLr = 24 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(47)=65.8psf1.4D = 1.4(47) = 65.8 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(47)+1.6(100)+0.5(24)=228.4psf1.2D + 1.6L + 0.5Lr = 1.2(47) + 1.6(100) + 0.5(24) = 228.4 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(47)+1.6(24)+1.0(100)=194.8psf1.2D + 1.6Lr + 1.0L = 1.2(47) + 1.6(24) + 1.0(100) = 194.8 psf
  4. Compare — governing value is 228.4 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 228.4 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 171.0 psf (service loads added without factors)
  • 65.8 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 5
Governing LRFD (strength) load combination — Basic combinations (5)

A floor system carries D = 77 psf, L = 64 psf and Lr = 22 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=77psfD = 77 psf
  • L=64psfL = 64 psf
  • Lr=22psfLr = 22 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(77)=107.8psf1.4D = 1.4(77) = 107.8 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(77)+1.6(64)+0.5(22)=205.8psf1.2D + 1.6L + 0.5Lr = 1.2(77) + 1.6(64) + 0.5(22) = 205.8 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(77)+1.6(22)+1.0(64)=191.6psf1.2D + 1.6Lr + 1.0L = 1.2(77) + 1.6(22) + 1.0(64) = 191.6 psf
  4. Compare — governing value is 205.8 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 205.8 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 163.0 psf (service loads added without factors)
  • 107.8 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 6
Governing LRFD (strength) load combination — Basic combinations (6)

A floor system carries D = 76 psf, L = 99 psf and Lr = 20 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=76psfD = 76 psf
  • L=99psfL = 99 psf
  • Lr=20psfLr = 20 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(76)=106.4psf1.4D = 1.4(76) = 106.4 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(76)+1.6(99)+0.5(20)=259.6psf1.2D + 1.6L + 0.5Lr = 1.2(76) + 1.6(99) + 0.5(20) = 259.6 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(76)+1.6(20)+1.0(99)=222.2psf1.2D + 1.6Lr + 1.0L = 1.2(76) + 1.6(20) + 1.0(99) = 222.2 psf
  4. Compare — governing value is 259.6 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 259.6 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 195.0 psf (service loads added without factors)
  • 106.4 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 7
Governing LRFD (strength) load combination — Basic combinations (7)

A floor system carries D = 54 psf, L = 73 psf and Lr = 22 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=54psfD = 54 psf
  • L=73psfL = 73 psf
  • Lr=22psfLr = 22 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(54)=75.6psf1.4D = 1.4(54) = 75.6 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(54)+1.6(73)+0.5(22)=192.6psf1.2D + 1.6L + 0.5Lr = 1.2(54) + 1.6(73) + 0.5(22) = 192.6 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(54)+1.6(22)+1.0(73)=173.0psf1.2D + 1.6Lr + 1.0L = 1.2(54) + 1.6(22) + 1.0(73) = 173.0 psf
  4. Compare — governing value is 192.6 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 192.6 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 149.0 psf (service loads added without factors)
  • 75.6 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 8
Governing LRFD (strength) load combination — Basic combinations (8)

A floor system carries D = 40 psf, L = 61 psf and Lr = 15 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=40psfD = 40 psf
  • L=61psfL = 61 psf
  • Lr=15psfLr = 15 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(40)=56.0psf1.4D = 1.4(40) = 56.0 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(40)+1.6(61)+0.5(15)=153.1psf1.2D + 1.6L + 0.5Lr = 1.2(40) + 1.6(61) + 0.5(15) = 153.1 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(40)+1.6(15)+1.0(61)=133.0psf1.2D + 1.6Lr + 1.0L = 1.2(40) + 1.6(15) + 1.0(61) = 133.0 psf
  4. Compare — governing value is 153.1 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 153.1 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 116.0 psf (service loads added without factors)
  • 56.0 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 9
Governing LRFD (strength) load combination — Basic combinations (9)

A floor system carries D = 48 psf, L = 57 psf and Lr = 15 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=48psfD = 48 psf
  • L=57psfL = 57 psf
  • Lr=15psfLr = 15 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(48)=67.2psf1.4D = 1.4(48) = 67.2 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(48)+1.6(57)+0.5(15)=156.3psf1.2D + 1.6L + 0.5Lr = 1.2(48) + 1.6(57) + 0.5(15) = 156.3 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(48)+1.6(15)+1.0(57)=138.6psf1.2D + 1.6Lr + 1.0L = 1.2(48) + 1.6(15) + 1.0(57) = 138.6 psf
  4. Compare — governing value is 156.3 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 156.3 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 120.0 psf (service loads added without factors)
  • 67.2 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

Example 10
Governing LRFD (strength) load combination — Basic combinations (10)

A floor system carries D = 42 psf, L = 54 psf and Lr = 18 psf. Evaluate the basic strength combinations and identify the governing factored load.

Given

  • D=42psfD = 42 psf
  • L=54psfL = 54 psf
  • Lr=18psfLr = 18 psf

Find

Governing factored load wu

Start with the thinking

  • Evaluate every applicable combination — the largest result governs.
  • Companion live load enters at 0.5L or 1.0L depending on the combination.

Step-by-step solution

  1. Combination 1

    1.4D=1.4(42)=58.8psf1.4D = 1.4(42) = 58.8 psf
  2. Combination 2

    1.2D+1.6L+0.5Lr=1.2(42)+1.6(54)+0.5(18)=145.8psf1.2D + 1.6L + 0.5Lr = 1.2(42) + 1.6(54) + 0.5(18) = 145.8 psf
  3. Combination 3

    1.2D+1.6Lr+1.0L=1.2(42)+1.6(18)+1.0(54)=133.2psf1.2D + 1.6Lr + 1.0L = 1.2(42) + 1.6(18) + 1.0(54) = 133.2 psf
  4. Compare — governing value is 145.8 psf from 1.2D + 1.6L + 0.5Lr

Answer:

wu ≈ 145.8 psf (1.2D + 1.6L + 0.5Lr governs)

Why the other options are there

  • 114.0 psf (service loads added without factors)
  • 58.8 psf (only 1.4D evaluated)

Reference: FE Reference Handbook — Structural Design → Basic combinations

© 2026 Dr. Steve Efe. Civil Engineering Capstone Studio. All rights reserved.