Skip to content

Blowers

Fluid Mechanics · FE Reference Handbook section

Fluid Mechanics
11 formulas
10 exam-style examples
~60 min
All Fluid Mechanics lectures

Core formulas for this FE topic

Definitions, applicability, units, assumptions and worked examples for each relation.

Worked exam-style examples

The four ways this section is written on the real exam — thoughts first, then equations, then substitution.

Example 1
Blowers (adiabatic power) — solve for blower power — Blowers

blowers used for aeration in a wastewater basin Given weight flow rate (w) = 1.5000 N/s; actual inlet temperature ratio factor (Q) = 1.0000; discharge pressure (p_2) = 227.0 kPa; inlet pressure (p_1) = 97.0000 kPa; efficiency (e) = 0.6100, determine the blower power (P) in kW.

Given

  • weightflowrate(w)=1.5000N/sweight flow rate (w) = 1.5000 N/s
  • actual inlet temperature ratio factor (Q) = 1.0000

  • dischargepressure(p2)=227.0kPadischarge pressure (p_2) = 227.0 kPa
  • inletpressure(p1)=97.0000kPainlet pressure (p_1) = 97.0000 kPa
  • efficiency(e)=0.6100efficiency (e) = 0.6100

Find

blower power (P), in kW

Start with the thinking

  • The governing relation printed in this handbook section is Blowers (adiabatic power).
  • Everything except P is given, so isolate P symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Blowers deliver air at modest pressure rise, and their power is estimated from an adiabatic compression relation.
D₁=120D₂=100inletdischarge

Figure 1 — schematic for Blowers (adiabatic power) — solve for blower power — Blowers

Step-by-step solution

  1. Step 1 — State the governing relation:

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]
  2. Step 2 — Rearrange the relation so that P stands alone on the left-hand side.

  3. Step 3 — List the givens: weight flow rate (w) = 1.5000 N/s, actual inlet temperature ratio factor (Q) = 1.0000, discharge pressure (p_2) = 227.0 kPa, inlet pressure (p_1) = 97.0000 kPa, efficiency (e) = 0.6100.

  4. Step 4 — Substitute the given values into the rearranged relation.

  5. Step 5 — Evaluate:

    P=0.0225 kWP = 0.0225\ \text{kW}
  6. Step 6 — Check: returning P = 0.0225 kW to

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]

    reproduces the given quantities, and both sides carry the same units.

Answer:
P=0.0225 kWP = 0.0225\ \text{kW}

Why the other options are there

  • 0.0450 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0113 — dropped that same factor in the other direction.
  • 0.0248 — rounded an intermediate value before the final step.

Reference: FE Handbook — Blowers

Example 2
Blower / compressor fluid power — solve for shaft power — Blowers (2)

a centrifugal blower on a dust-collection duct Given volumetric flow (Q) = 8.8000 m^3/s; pressure rise (\Delta p) = 22,500 Pa; efficiency (\eta) = 0.5900, determine the shaft power (W) in W.

Given

  • volumetricflow(Q)=8.8000m3/svolumetric flow (Q) = 8.8000 m^3/s
  • pressurerise(Δp)=22,500Papressure rise (\Delta p) = 22,500 Pa
  • efficiency(η)=0.5900efficiency (\eta) = 0.5900

Find

shaft power (W), in W

Start with the thinking

  • The governing relation printed in this handbook section is Blower / compressor fluid power.
  • Everything except W is given, so isolate W symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • A blower raises the pressure of an air stream across an aeration basin diffuser system.

Step-by-step solution

  1. Step 1 — State the governing relation:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  2. Step 2 — Rearrange symbolically for W:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  3. Step 3 — List the givens: volumetric flow (Q) = 8.8000 m^3/s, pressure rise (\Delta p) = 22,500 Pa, efficiency (\eta) = 0.5900.

  4. Step 4 — Substitute the given values:

    W=8.8000225000.5900W = \dfrac{8.8000 22500}{0.5900}
  5. Step 5 — Evaluate:

    W=335593 WW = 335593\ \text{W}
  6. Step 6 — Check: returning W = 335,593 W to

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}

    reproduces the given quantities, and both sides carry the same units.

Answer:
W=335593 WW = 335593\ \text{W}

Why the other options are there

  • 671,186 — kept a factor of two that cancels in the correct rearrangement.
  • 167,797 — dropped that same factor in the other direction.
  • 369,153 — rounded an intermediate value before the final step.

Reference: FE Handbook — Fans, Blowers, and Compressors

Example 3
Blowers (adiabatic power) — solve for efficiency — Blowers (3)

blowers supplying combustion air at low pressure rise Given weight flow rate (w) = 12.5000 N/s; actual inlet temperature ratio factor (Q) = 1.0000; discharge pressure (p_2) = 164.0 kPa; inlet pressure (p_1) = 97.5000 kPa; blower power (P) = 104.0 kW, determine the efficiency (e).

Given

  • weightflowrate(w)=12.5000N/sweight flow rate (w) = 12.5000 N/s
  • actual inlet temperature ratio factor (Q) = 1.0000

  • dischargepressure(p2)=164.0kPadischarge pressure (p_2) = 164.0 kPa
  • inletpressure(p1)=97.5000kPainlet pressure (p_1) = 97.5000 kPa
  • blowerpower(P)=104.0kWblower power (P) = 104.0 kW

Find

efficiency (e)

Start with the thinking

  • The governing relation printed in this handbook section is Blowers (adiabatic power).
  • Everything except e is given, so isolate e symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Blowers deliver air at modest pressure rise, and their power is estimated from an adiabatic compression relation.
D₁=120D₂=100inletdischarge

Figure 3 — schematic for Blowers (adiabatic power) — solve for efficiency — Blowers (3)

Step-by-step solution

  1. Step 1 — State the governing relation:

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]
  2. Step 2 — Rearrange the relation so that e stands alone on the left-hand side.

  3. Step 3 — List the givens: weight flow rate (w) = 12.5000 N/s, actual inlet temperature ratio factor (Q) = 1.0000, discharge pressure (p_2) = 164.0 kPa, inlet pressure (p_1) = 97.5000 kPa, blower power (P) = 104.0 kW.

  4. Step 4 — Substitute the given values into the rearranged relation.

  5. Step 5 — Evaluate:

    e=0.0006e = 0.0006
  6. Step 6 — Check: returning e = 0.0006 to

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]

    reproduces the given quantities, and both sides carry the same units.

Answer:
e=0.0006e = 0.0006

Why the other options are there

  • 0.0013 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0003 — dropped that same factor in the other direction.
  • 0.0007 — rounded an intermediate value before the final step.

Reference: FE Handbook — Blowers

Example 4
Blower / compressor fluid power — solve for volumetric flow — Blowers (4)

a compressor supplying pneumatic construction tools Given shaft power (W) = 176,326 W; pressure rise (\Delta p) = 38,800 Pa; efficiency (\eta) = 0.6900, determine the volumetric flow (Q) in m^3/s.

Given

  • shaftpower(W)=176,326Wshaft power (W) = 176,326 W
  • pressurerise(Δp)=38,800Papressure rise (\Delta p) = 38,800 Pa
  • efficiency(η)=0.6900efficiency (\eta) = 0.6900

Find

volumetric flow (Q), in m^3/s

Start with the thinking

  • The governing relation printed in this handbook section is Blower / compressor fluid power.
  • Everything except Q is given, so isolate Q symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • A blower raises the pressure of an air stream across an aeration basin diffuser system.

Step-by-step solution

  1. Step 1 — State the governing relation:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  2. Step 2 — Rearrange symbolically for Q:

    Q=WηΔpQ = \dfrac{W \eta}{\Delta p}
  3. Step 3 — List the givens: shaft power (W) = 176,326 W, pressure rise (\Delta p) = 38,800 Pa, efficiency (\eta) = 0.6900.

  4. Step 4 — Substitute the given values:

    Q=1763260.690038800Q = \dfrac{176326 0.6900}{38800}
  5. Step 5 — Evaluate:

    Q = 3.1357\ \text{m^3/s}
  6. Step 6 — Check: returning Q = 3.1357 m^3/s to

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}

    reproduces the given quantities, and both sides carry the same units.

Answer:
Q = 3.1357\ \text{m^3/s}

Why the other options are there

  • 6.2714 — kept a factor of two that cancels in the correct rearrangement.
  • 1.5678 — dropped that same factor in the other direction.
  • 3.4493 — rounded an intermediate value before the final step.

Reference: FE Handbook — Fans, Blowers, and Compressors

Example 5
Blowers (adiabatic power) — solve for blower power (case 2) — Blowers (5)

blowers moving air through ductwork at elevated pressure Given weight flow rate (w) = 4.0000 N/s; actual inlet temperature ratio factor (Q) = 1.0000; discharge pressure (p_2) = 195.0 kPa; inlet pressure (p_1) = 95.5000 kPa; efficiency (e) = 0.8700, determine the blower power (P) in kW.

Given

  • weightflowrate(w)=4.0000N/sweight flow rate (w) = 4.0000 N/s
  • actual inlet temperature ratio factor (Q) = 1.0000

  • dischargepressure(p2)=195.0kPadischarge pressure (p_2) = 195.0 kPa
  • inletpressure(p1)=95.5000kPainlet pressure (p_1) = 95.5000 kPa
  • efficiency(e)=0.8700efficiency (e) = 0.8700

Find

blower power (P), in kW

Start with the thinking

  • The governing relation printed in this handbook section is Blowers (adiabatic power).
  • Everything except P is given, so isolate P symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Blowers deliver air at modest pressure rise, and their power is estimated from an adiabatic compression relation.
D₁=120D₂=100inletdischarge

Figure 5 — schematic for Blowers (adiabatic power) — solve for blower power (case 2) — Blowers (5)

Step-by-step solution

  1. Step 1 — State the governing relation:

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]
  2. Step 2 — Rearrange the relation so that P stands alone on the left-hand side.

  3. Step 3 — List the givens: weight flow rate (w) = 4.0000 N/s, actual inlet temperature ratio factor (Q) = 1.0000, discharge pressure (p_2) = 195.0 kPa, inlet pressure (p_1) = 95.5000 kPa, efficiency (e) = 0.8700.

  4. Step 4 — Substitute the given values into the rearranged relation.

  5. Step 5 — Evaluate:

    P=0.0347 kWP = 0.0347\ \text{kW}
  6. Step 6 — Check: returning P = 0.0347 kW to

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]

    reproduces the given quantities, and both sides carry the same units.

Answer:
P=0.0347 kWP = 0.0347\ \text{kW}

Why the other options are there

  • 0.0693 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0173 — dropped that same factor in the other direction.
  • 0.0381 — rounded an intermediate value before the final step.

Reference: FE Handbook — Blowers

Example 6
Blower / compressor fluid power — solve for efficiency — Blowers (6)

a positive-displacement blower feeding an aeration basin Given shaft power (W) = 102,017 W; volumetric flow (Q) = 10.4000 m^3/s; pressure rise (\Delta p) = 20,500 Pa, determine the efficiency (\eta).

Given

  • shaftpower(W)=102,017Wshaft power (W) = 102,017 W
  • volumetricflow(Q)=10.4000m3/svolumetric flow (Q) = 10.4000 m^3/s
  • pressurerise(Δp)=20,500Papressure rise (\Delta p) = 20,500 Pa

Find

efficiency (\eta)

Start with the thinking

  • The governing relation printed in this handbook section is Blower / compressor fluid power.
  • Everything except \eta is given, so isolate \eta symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • A blower raises the pressure of an air stream across an aeration basin diffuser system.

Step-by-step solution

  1. Step 1 — State the governing relation:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  2. Step 2 — Rearrange symbolically for \eta:

    η=QΔpW\eta = \dfrac{Q \Delta p}{W}
  3. Step 3 — List the givens: shaft power (W) = 102,017 W, volumetric flow (Q) = 10.4000 m^3/s, pressure rise (\Delta p) = 20,500 Pa.

  4. Step 4 — Substitute the given values:

    η=10.400020500102017\eta = \dfrac{10.4000 20500}{102017}
  5. Step 5 — Evaluate:

    η=2.0898\eta = 2.0898
  6. Step 6 — Check: returning \eta = 2.0898 to

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}

    reproduces the given quantities, and both sides carry the same units.

Answer:
η=2.0898\eta = 2.0898

Why the other options are there

  • 4.1797 — kept a factor of two that cancels in the correct rearrangement.
  • 1.0449 — dropped that same factor in the other direction.
  • 2.2988 — rounded an intermediate value before the final step.

Reference: FE Handbook — Fans, Blowers, and Compressors

Example 7
Blowers (adiabatic power) — solve for efficiency (case 2) — Blowers (7)

blowers used for aeration in a wastewater basin Given weight flow rate (w) = 19.0000 N/s; actual inlet temperature ratio factor (Q) = 1.0000; discharge pressure (p_2) = 162.0 kPa; inlet pressure (p_1) = 97.0000 kPa; blower power (P) = 174.0 kW, determine the efficiency (e).

Given

  • weightflowrate(w)=19.0000N/sweight flow rate (w) = 19.0000 N/s
  • actual inlet temperature ratio factor (Q) = 1.0000

  • dischargepressure(p2)=162.0kPadischarge pressure (p_2) = 162.0 kPa
  • inletpressure(p1)=97.0000kPainlet pressure (p_1) = 97.0000 kPa
  • blowerpower(P)=174.0kWblower power (P) = 174.0 kW

Find

efficiency (e)

Start with the thinking

  • The governing relation printed in this handbook section is Blowers (adiabatic power).
  • Everything except e is given, so isolate e symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Blowers deliver air at modest pressure rise, and their power is estimated from an adiabatic compression relation.
D₁=120D₂=100inletdischarge

Figure 7 — schematic for Blowers (adiabatic power) — solve for efficiency (case 2) — Blowers (7)

Step-by-step solution

  1. Step 1 — State the governing relation:

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]
  2. Step 2 — Rearrange the relation so that e stands alone on the left-hand side.

  3. Step 3 — List the givens: weight flow rate (w) = 19.0000 N/s, actual inlet temperature ratio factor (Q) = 1.0000, discharge pressure (p_2) = 162.0 kPa, inlet pressure (p_1) = 97.0000 kPa, blower power (P) = 174.0 kW.

  4. Step 4 — Substitute the given values into the rearranged relation.

  5. Step 5 — Evaluate:

    e=0.0006e = 0.0006
  6. Step 6 — Check: returning e = 0.0006 to

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]

    reproduces the given quantities, and both sides carry the same units.

Answer:
e=0.0006e = 0.0006

Why the other options are there

  • 0.0011 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0003 — dropped that same factor in the other direction.
  • 0.0006 — rounded an intermediate value before the final step.

Reference: FE Handbook — Blowers

Example 8
Blower / compressor fluid power — solve for shaft power (case 2) — Blowers (8)

a centrifugal blower on a dust-collection duct Given volumetric flow (Q) = 3.8000 m^3/s; pressure rise (\Delta p) = 34,200 Pa; efficiency (\eta) = 0.6000, determine the shaft power (W) in W.

Given

  • volumetricflow(Q)=3.8000m3/svolumetric flow (Q) = 3.8000 m^3/s
  • pressurerise(Δp)=34,200Papressure rise (\Delta p) = 34,200 Pa
  • efficiency(η)=0.6000efficiency (\eta) = 0.6000

Find

shaft power (W), in W

Start with the thinking

  • The governing relation printed in this handbook section is Blower / compressor fluid power.
  • Everything except W is given, so isolate W symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • A blower raises the pressure of an air stream across an aeration basin diffuser system.

Step-by-step solution

  1. Step 1 — State the governing relation:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  2. Step 2 — Rearrange symbolically for W:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  3. Step 3 — List the givens: volumetric flow (Q) = 3.8000 m^3/s, pressure rise (\Delta p) = 34,200 Pa, efficiency (\eta) = 0.6000.

  4. Step 4 — Substitute the given values:

    W=3.8000342000.6000W = \dfrac{3.8000 34200}{0.6000}
  5. Step 5 — Evaluate:

    W=216600 WW = 216600\ \text{W}
  6. Step 6 — Check: returning W = 216,600 W to

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}

    reproduces the given quantities, and both sides carry the same units.

Answer:
W=216600 WW = 216600\ \text{W}

Why the other options are there

  • 433,200 — kept a factor of two that cancels in the correct rearrangement.
  • 108,300 — dropped that same factor in the other direction.
  • 238,260 — rounded an intermediate value before the final step.

Reference: FE Handbook — Fans, Blowers, and Compressors

Example 9
Blowers (adiabatic power) — solve for blower power (case 3) — Blowers (9)

blowers supplying combustion air at low pressure rise Given weight flow rate (w) = 8.5000 N/s; actual inlet temperature ratio factor (Q) = 1.0000; discharge pressure (p_2) = 192.0 kPa; inlet pressure (p_1) = 98.5000 kPa; efficiency (e) = 0.7800, determine the blower power (P) in kW.

Given

  • weightflowrate(w)=8.5000N/sweight flow rate (w) = 8.5000 N/s
  • actual inlet temperature ratio factor (Q) = 1.0000

  • dischargepressure(p2)=192.0kPadischarge pressure (p_2) = 192.0 kPa
  • inletpressure(p1)=98.5000kPainlet pressure (p_1) = 98.5000 kPa
  • efficiency(e)=0.7800efficiency (e) = 0.7800

Find

blower power (P), in kW

Start with the thinking

  • The governing relation printed in this handbook section is Blowers (adiabatic power).
  • Everything except P is given, so isolate P symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Blowers deliver air at modest pressure rise, and their power is estimated from an adiabatic compression relation.
D₁=120D₂=100inletdischarge

Figure 9 — schematic for Blowers (adiabatic power) — solve for blower power (case 3) — Blowers (9)

Step-by-step solution

  1. Step 1 — State the governing relation:

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]
  2. Step 2 — Rearrange the relation so that P stands alone on the left-hand side.

  3. Step 3 — List the givens: weight flow rate (w) = 8.5000 N/s, actual inlet temperature ratio factor (Q) = 1.0000, discharge pressure (p_2) = 192.0 kPa, inlet pressure (p_1) = 98.5000 kPa, efficiency (e) = 0.7800.

  4. Step 4 — Substitute the given values into the rearranged relation.

  5. Step 5 — Evaluate:

    P=0.0763 kWP = 0.0763\ \text{kW}
  6. Step 6 — Check: returning P = 0.0763 kW to

    P=wQ29.7e[(p2p1)0.283−1]P = \dfrac{w Q}{29.7 e} \left[ \left(\dfrac{p_2}{p_1}\right)^{0.283} - 1 \right]

    reproduces the given quantities, and both sides carry the same units.

Answer:
P=0.0763 kWP = 0.0763\ \text{kW}

Why the other options are there

  • 0.1526 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0381 — dropped that same factor in the other direction.
  • 0.0839 — rounded an intermediate value before the final step.

Reference: FE Handbook — Blowers

Example 10
Blower / compressor fluid power — solve for volumetric flow (case 2) — Blowers (10)

a compressor supplying pneumatic construction tools Given shaft power (W) = 181,731 W; pressure rise (\Delta p) = 16,700 Pa; efficiency (\eta) = 0.8100, determine the volumetric flow (Q) in m^3/s.

Given

  • shaftpower(W)=181,731Wshaft power (W) = 181,731 W
  • pressurerise(Δp)=16,700Papressure rise (\Delta p) = 16,700 Pa
  • efficiency(η)=0.8100efficiency (\eta) = 0.8100

Find

volumetric flow (Q), in m^3/s

Start with the thinking

  • The governing relation printed in this handbook section is Blower / compressor fluid power.
  • Everything except Q is given, so isolate Q symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • A blower raises the pressure of an air stream across an aeration basin diffuser system.

Step-by-step solution

  1. Step 1 — State the governing relation:

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}
  2. Step 2 — Rearrange symbolically for Q:

    Q=WηΔpQ = \dfrac{W \eta}{\Delta p}
  3. Step 3 — List the givens: shaft power (W) = 181,731 W, pressure rise (\Delta p) = 16,700 Pa, efficiency (\eta) = 0.8100.

  4. Step 4 — Substitute the given values:

    Q=1817310.810016700Q = \dfrac{181731 0.8100}{16700}
  5. Step 5 — Evaluate:

    Q = 8.8145\ \text{m^3/s}
  6. Step 6 — Check: returning Q = 8.8145 m^3/s to

    W=QΔpηW = \dfrac{Q \Delta p}{\eta}

    reproduces the given quantities, and both sides carry the same units.

Answer:
Q = 8.8145\ \text{m^3/s}

Why the other options are there

  • 17.6290 — kept a factor of two that cancels in the correct rearrangement.
  • 4.4072 — dropped that same factor in the other direction.
  • 9.6959 — rounded an intermediate value before the final step.

Reference: FE Handbook — Fans, Blowers, and Compressors

© 2026 Dr. Steve Efe. Civil Engineering Capstone Studio. All rights reserved.