Skip to content

Water Flux

Environmental Engineering · FE Reference Handbook section

Environmental Engineering
5 formulas
10 exam-style examples
~55 min
All Environmental Engineering lectures

Core formulas for this FE topic

Definitions, applicability, units, assumptions and worked examples for each relation.

Worked exam-style examples

The four ways this section is written on the real exam — thoughts first, then equations, then substitution.

Example 1
Water Flux — solve for water flux — Water Flux

water flux across a reverse osmosis membrane in desalination Given membrane permeability coefficient (K_w) = 0.0081 m/day/kPa; applied pressure differential (deltaP) = 2,060 kPa; osmotic pressure differential (deltapi) = 1,110 kPa, determine the water flux (F_w) in m/day.

Given

  • membranepermeabilitycoefficient(Kw)=0.0081m/day/kPamembrane permeability coefficient (K_w) = 0.0081 m/day/kPa
  • appliedpressuredifferential(deltaP)=2,060kPaapplied pressure differential (deltaP) = 2,060 kPa
  • osmoticpressuredifferential(deltapi)=1,110kPaosmotic pressure differential (deltapi) = 1,110 kPa

Find

water flux (F_w), in m/day

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except F_w is given, so isolate F_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for F_w:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0081 m/day/kPa, applied pressure differential (deltaP) = 2,060 kPa, osmotic pressure differential (deltapi) = 1,110 kPa.

  4. Step 4 — Substitute the given values:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  5. Step 5 — Evaluate:

    Fw=7.6950 m/dayF_{w} = 7.6950\ \text{m/day}
  6. Step 6 — Check: returning F_w = 7.6950 m/day to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Fw=7.6950 m/dayF_{w} = 7.6950\ \text{m/day}

Why the other options are there

  • 15.3900 — kept a factor of two that cancels in the correct rearrangement.
  • 3.8475 — dropped that same factor in the other direction.
  • 8.4645 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 2
Water Flux — solve for membrane permeability coefficient — Water Flux (2)

water flux through the membrane driven by net applied pressure Given applied pressure differential (deltaP) = 1,020 kPa; osmotic pressure differential (deltapi) = 800.0 kPa; water flux (F_w) = 70.0500 m/day, determine the membrane permeability coefficient (K_w) in m/day/kPa.

Given

  • appliedpressuredifferential(deltaP)=1,020kPaapplied pressure differential (deltaP) = 1,020 kPa
  • osmoticpressuredifferential(deltapi)=800.0kPaosmotic pressure differential (deltapi) = 800.0 kPa
  • waterflux(Fw)=70.0500m/daywater flux (F_w) = 70.0500 m/day

Find

membrane permeability coefficient (K_w), in m/day/kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except K_w is given, so isolate K_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for K_w:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  3. Step 3 — List the givens: applied pressure differential (deltaP) = 1,020 kPa, osmotic pressure differential (deltapi) = 800.0 kPa, water flux (F_w) = 70.0500 m/day.

  4. Step 4 — Substitute the given values:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  5. Step 5 — Evaluate:

    Kw=0.3184 m/day/kPaK_{w} = 0.3184\ \text{m/day/kPa}
  6. Step 6 — Check: returning K_w = 0.3184 m/day/kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Kw=0.3184 m/day/kPaK_{w} = 0.3184\ \text{m/day/kPa}

Why the other options are there

  • 0.6368 — kept a factor of two that cancels in the correct rearrangement.
  • 0.1592 — dropped that same factor in the other direction.
  • 0.3503 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 3
Water Flux — solve for applied pressure differential — Water Flux (3)

water flux calculation for a membrane treatment system Given membrane permeability coefficient (K_w) = 0.0334 m/day/kPa; osmotic pressure differential (deltapi) = 350.0 kPa; water flux (F_w) = 76.2200 m/day, determine the applied pressure differential (deltaP) in kPa.

Given

  • membranepermeabilitycoefficient(Kw)=0.0334m/day/kPamembrane permeability coefficient (K_w) = 0.0334 m/day/kPa
  • osmoticpressuredifferential(deltapi)=350.0kPaosmotic pressure differential (deltapi) = 350.0 kPa
  • waterflux(Fw)=76.2200m/daywater flux (F_w) = 76.2200 m/day

Find

applied pressure differential (deltaP), in kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except deltaP is given, so isolate deltaP symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for deltaP:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0334 m/day/kPa, osmotic pressure differential (deltapi) = 350.0 kPa, water flux (F_w) = 76.2200 m/day.

  4. Step 4 — Substitute the given values:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  5. Step 5 — Evaluate:

    deltaP=2632 kPadeltaP = 2632\ \text{kPa}
  6. Step 6 — Check: returning deltaP = 2,632 kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
deltaP=2632 kPadeltaP = 2632\ \text{kPa}

Why the other options are there

  • 5,264 — kept a factor of two that cancels in the correct rearrangement.
  • 1,316 — dropped that same factor in the other direction.
  • 2,895 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 4
Water Flux — solve for water flux (case 2) — Water Flux (4)

water flux across a reverse osmosis membrane in desalination Given membrane permeability coefficient (K_w) = 0.0130 m/day/kPa; applied pressure differential (deltaP) = 1,050 kPa; osmotic pressure differential (deltapi) = 1,140 kPa, determine the water flux (F_w) in m/day.

Given

  • membranepermeabilitycoefficient(Kw)=0.0130m/day/kPamembrane permeability coefficient (K_w) = 0.0130 m/day/kPa
  • appliedpressuredifferential(deltaP)=1,050kPaapplied pressure differential (deltaP) = 1,050 kPa
  • osmoticpressuredifferential(deltapi)=1,140kPaosmotic pressure differential (deltapi) = 1,140 kPa

Find

water flux (F_w), in m/day

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except F_w is given, so isolate F_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for F_w:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0130 m/day/kPa, applied pressure differential (deltaP) = 1,050 kPa, osmotic pressure differential (deltapi) = 1,140 kPa.

  4. Step 4 — Substitute the given values:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  5. Step 5 — Evaluate:

    Fw=−1.1700 m/dayF_{w} = -1.1700\ \text{m/day}
  6. Step 6 — Check: returning F_w = -1.1700 m/day to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Fw=−1.1700 m/dayF_{w} = -1.1700\ \text{m/day}

Why the other options are there

  • -2.3400 — kept a factor of two that cancels in the correct rearrangement.
  • -0.5850 — dropped that same factor in the other direction.
  • -1.2870 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 5
Water Flux — solve for membrane permeability coefficient (case 2) — Water Flux (5)

water flux through the membrane driven by net applied pressure Given applied pressure differential (deltaP) = 3,890 kPa; osmotic pressure differential (deltapi) = 400.0 kPa; water flux (F_w) = 95.1500 m/day, determine the membrane permeability coefficient (K_w) in m/day/kPa.

Given

  • appliedpressuredifferential(deltaP)=3,890kPaapplied pressure differential (deltaP) = 3,890 kPa
  • osmoticpressuredifferential(deltapi)=400.0kPaosmotic pressure differential (deltapi) = 400.0 kPa
  • waterflux(Fw)=95.1500m/daywater flux (F_w) = 95.1500 m/day

Find

membrane permeability coefficient (K_w), in m/day/kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except K_w is given, so isolate K_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for K_w:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  3. Step 3 — List the givens: applied pressure differential (deltaP) = 3,890 kPa, osmotic pressure differential (deltapi) = 400.0 kPa, water flux (F_w) = 95.1500 m/day.

  4. Step 4 — Substitute the given values:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  5. Step 5 — Evaluate:

    Kw=0.0273 m/day/kPaK_{w} = 0.0273\ \text{m/day/kPa}
  6. Step 6 — Check: returning K_w = 0.0273 m/day/kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Kw=0.0273 m/day/kPaK_{w} = 0.0273\ \text{m/day/kPa}

Why the other options are there

  • 0.0545 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0136 — dropped that same factor in the other direction.
  • 0.0300 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 6
Water Flux — solve for applied pressure differential (case 2) — Water Flux (6)

water flux calculation for a membrane treatment system Given membrane permeability coefficient (K_w) = 0.0456 m/day/kPa; osmotic pressure differential (deltapi) = 370.0 kPa; water flux (F_w) = 56.8500 m/day, determine the applied pressure differential (deltaP) in kPa.

Given

  • membranepermeabilitycoefficient(Kw)=0.0456m/day/kPamembrane permeability coefficient (K_w) = 0.0456 m/day/kPa
  • osmoticpressuredifferential(deltapi)=370.0kPaosmotic pressure differential (deltapi) = 370.0 kPa
  • waterflux(Fw)=56.8500m/daywater flux (F_w) = 56.8500 m/day

Find

applied pressure differential (deltaP), in kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except deltaP is given, so isolate deltaP symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for deltaP:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0456 m/day/kPa, osmotic pressure differential (deltapi) = 370.0 kPa, water flux (F_w) = 56.8500 m/day.

  4. Step 4 — Substitute the given values:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  5. Step 5 — Evaluate:

    deltaP=1617 kPadeltaP = 1617\ \text{kPa}
  6. Step 6 — Check: returning deltaP = 1,617 kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
deltaP=1617 kPadeltaP = 1617\ \text{kPa}

Why the other options are there

  • 3,233 — kept a factor of two that cancels in the correct rearrangement.
  • 808.4 — dropped that same factor in the other direction.
  • 1,778 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 7
Water Flux — solve for water flux (case 3) — Water Flux (7)

water flux across a reverse osmosis membrane in desalination Given membrane permeability coefficient (K_w) = 0.0075 m/day/kPa; applied pressure differential (deltaP) = 2,800 kPa; osmotic pressure differential (deltapi) = 510.0 kPa, determine the water flux (F_w) in m/day.

Given

  • membranepermeabilitycoefficient(Kw)=0.0075m/day/kPamembrane permeability coefficient (K_w) = 0.0075 m/day/kPa
  • appliedpressuredifferential(deltaP)=2,800kPaapplied pressure differential (deltaP) = 2,800 kPa
  • osmoticpressuredifferential(deltapi)=510.0kPaosmotic pressure differential (deltapi) = 510.0 kPa

Find

water flux (F_w), in m/day

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except F_w is given, so isolate F_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for F_w:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0075 m/day/kPa, applied pressure differential (deltaP) = 2,800 kPa, osmotic pressure differential (deltapi) = 510.0 kPa.

  4. Step 4 — Substitute the given values:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  5. Step 5 — Evaluate:

    Fw=17.1750 m/dayF_{w} = 17.1750\ \text{m/day}
  6. Step 6 — Check: returning F_w = 17.1750 m/day to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Fw=17.1750 m/dayF_{w} = 17.1750\ \text{m/day}

Why the other options are there

  • 34.3500 — kept a factor of two that cancels in the correct rearrangement.
  • 8.5875 — dropped that same factor in the other direction.
  • 18.8925 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 8
Water Flux — solve for membrane permeability coefficient (case 3) — Water Flux (8)

water flux through the membrane driven by net applied pressure Given applied pressure differential (deltaP) = 2,300 kPa; osmotic pressure differential (deltapi) = 1,260 kPa; water flux (F_w) = 31.3000 m/day, determine the membrane permeability coefficient (K_w) in m/day/kPa.

Given

  • appliedpressuredifferential(deltaP)=2,300kPaapplied pressure differential (deltaP) = 2,300 kPa
  • osmoticpressuredifferential(deltapi)=1,260kPaosmotic pressure differential (deltapi) = 1,260 kPa
  • waterflux(Fw)=31.3000m/daywater flux (F_w) = 31.3000 m/day

Find

membrane permeability coefficient (K_w), in m/day/kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except K_w is given, so isolate K_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for K_w:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  3. Step 3 — List the givens: applied pressure differential (deltaP) = 2,300 kPa, osmotic pressure differential (deltapi) = 1,260 kPa, water flux (F_w) = 31.3000 m/day.

  4. Step 4 — Substitute the given values:

    Kw=FwΔP−ΔπK_{w} = \dfrac{F_w}{\Delta P-\Delta \pi}
  5. Step 5 — Evaluate:

    Kw=0.0301 m/day/kPaK_{w} = 0.0301\ \text{m/day/kPa}
  6. Step 6 — Check: returning K_w = 0.0301 m/day/kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Kw=0.0301 m/day/kPaK_{w} = 0.0301\ \text{m/day/kPa}

Why the other options are there

  • 0.0602 — kept a factor of two that cancels in the correct rearrangement.
  • 0.0150 — dropped that same factor in the other direction.
  • 0.0331 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 9
Water Flux — solve for applied pressure differential (case 3) — Water Flux (9)

water flux calculation for a membrane treatment system Given membrane permeability coefficient (K_w) = 0.0492 m/day/kPa; osmotic pressure differential (deltapi) = 1,410 kPa; water flux (F_w) = 97.5400 m/day, determine the applied pressure differential (deltaP) in kPa.

Given

  • membranepermeabilitycoefficient(Kw)=0.0492m/day/kPamembrane permeability coefficient (K_w) = 0.0492 m/day/kPa
  • osmoticpressuredifferential(deltapi)=1,410kPaosmotic pressure differential (deltapi) = 1,410 kPa
  • waterflux(Fw)=97.5400m/daywater flux (F_w) = 97.5400 m/day

Find

applied pressure differential (deltaP), in kPa

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except deltaP is given, so isolate deltaP symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for deltaP:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0492 m/day/kPa, osmotic pressure differential (deltapi) = 1,410 kPa, water flux (F_w) = 97.5400 m/day.

  4. Step 4 — Substitute the given values:

    deltaP=FwKw+ΔπdeltaP = \dfrac{F_w}{K_w}+\Delta\pi
  5. Step 5 — Evaluate:

    deltaP=3393 kPadeltaP = 3393\ \text{kPa}
  6. Step 6 — Check: returning deltaP = 3,393 kPa to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
deltaP=3393 kPadeltaP = 3393\ \text{kPa}

Why the other options are there

  • 6,785 — kept a factor of two that cancels in the correct rearrangement.
  • 1,696 — dropped that same factor in the other direction.
  • 3,732 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

Example 10
Water Flux — solve for water flux (case 4) — Water Flux (10)

water flux across a reverse osmosis membrane in desalination Given membrane permeability coefficient (K_w) = 0.0374 m/day/kPa; applied pressure differential (deltaP) = 1,710 kPa; osmotic pressure differential (deltapi) = 1,120 kPa, determine the water flux (F_w) in m/day.

Given

  • membranepermeabilitycoefficient(Kw)=0.0374m/day/kPamembrane permeability coefficient (K_w) = 0.0374 m/day/kPa
  • appliedpressuredifferential(deltaP)=1,710kPaapplied pressure differential (deltaP) = 1,710 kPa
  • osmoticpressuredifferential(deltapi)=1,120kPaosmotic pressure differential (deltapi) = 1,120 kPa

Find

water flux (F_w), in m/day

Start with the thinking

  • The governing relation printed in this handbook section is Water Flux.
  • Everything except F_w is given, so isolate F_w symbolically first — never rearrange after the numbers are in.
  • Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
  • Water flux across a reverse osmosis membrane is driven by the net pressure differential minus the osmotic pressure differential.

Step-by-step solution

  1. Step 1 — State the governing relation:

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)
  2. Step 2 — Rearrange symbolically for F_w:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  3. Step 3 — List the givens: membrane permeability coefficient (K_w) = 0.0374 m/day/kPa, applied pressure differential (deltaP) = 1,710 kPa, osmotic pressure differential (deltapi) = 1,120 kPa.

  4. Step 4 — Substitute the given values:

    Fw=Kw(ΔP−Δπ)F_{w} = K_w(\Delta P-\Delta \pi)
  5. Step 5 — Evaluate:

    Fw=22.0660 m/dayF_{w} = 22.0660\ \text{m/day}
  6. Step 6 — Check: returning F_w = 22.0660 m/day to

    Fw=Kw(ΔP−Δπ)F_w = K_w (\Delta P - \Delta \pi)

    reproduces the given quantities, and both sides carry the same units.

Answer:
Fw=22.0660 m/dayF_{w} = 22.0660\ \text{m/day}

Why the other options are there

  • 44.1320 — kept a factor of two that cancels in the correct rearrangement.
  • 11.0330 — dropped that same factor in the other direction.
  • 24.2726 — rounded an intermediate value before the final step.

Reference: FE Handbook — Water Flux

© 2026 Dr. Steve Efe. Civil Engineering Capstone Studio. All rights reserved.