Aerobic Digestion
Environmental Engineering · FE Reference Handbook section
Handbook notes for this section
Definitions and conditions exactly as the handbook states them.
- Design criteria for aerobic digestersa
- Energy requirements for mixing
- Reduction in volatile suspended solids (VSS) (%) 40–50
Core formulas for this FE topic
Definitions, applicability, units, assumptions and worked examples for each relation.
This section is conceptual; there are no equations to memorise.
Worked exam-style examples
The four ways this section is written on the real exam — thoughts first, then equations, then substitution.
aerobic digestion tank volume for waste activated sludge stabilization Given influent sludge flow (Q_i) = 233.0 m^3/day; influent volatile solids (X_i) = 19,940 mg/L; BOD fraction factor (F) = 0.5900; influent BOD5 (S_i) = 370.0 mg/L; digester volatile solids (X_d) = 13,420 mg/L; reaction rate constant (K_d) = 0.1420 1/day; volatile fraction (P_v) = 0.6900; digester detention time (theta_c) = 32.5000 day, determine the digester volume (V_d) in m^3.
Given
influent sludge flow (Q_i) = 233.0 m^3/day
influent volatile solids (X_i) = 19,940 mg/L
influent BOD5 (S_i) = 370.0 mg/L
Find
digester volume (V_d), in m^3
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except V_d is given, so isolate V_d symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 1 — schematic for Aerobic Digestion — solve for digester volume — Aerobic Digestion
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for V_d:
Step 3 — List the givens: influent sludge flow (Q_i) = 233.0 m^3/day, influent volatile solids (X_i) = 19,940 mg/L, BOD fraction factor (F) = 0.5900, influent BOD5 (S_i) = 370.0 mg/L, digester volatile solids (X_d) = 13,420 mg/L, reaction rate constant (K_d) = 0.1420 1/day, volatile fraction (P_v) = 0.6900, digester detention time (theta_c) = 32.5000 day.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
V_{d} = 2718\ \text{m^3}Step 6 — Check: returning V_d = 2,718 m^3 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 5,437 — kept a factor of two that cancels in the correct rearrangement.
- 1,359 — dropped that same factor in the other direction.
- 2,990 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion design of a sludge digester Given influent volatile solids (X_i) = 12,510 mg/L; BOD fraction factor (F) = 0.6300; influent BOD5 (S_i) = 770.0 mg/L; digester volatile solids (X_d) = 9,310 mg/L; reaction rate constant (K_d) = 0.1380 1/day; volatile fraction (P_v) = 0.6300; digester detention time (theta_c) = 20.0000 day; digester volume (V_d) = 13,299 m^3, determine the influent sludge flow (Q_i) in m^3/day.
Given
influent volatile solids (X_i) = 12,510 mg/L
influent BOD5 (S_i) = 770.0 mg/L
Find
influent sludge flow (Q_i), in m^3/day
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except Q_i is given, so isolate Q_i symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 2 — schematic for Aerobic Digestion — solve for influent sludge flow — Aerobic Digestion (2)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for Q_i:
Step 3 — List the givens: influent volatile solids (X_i) = 12,510 mg/L, BOD fraction factor (F) = 0.6300, influent BOD5 (S_i) = 770.0 mg/L, digester volatile solids (X_d) = 9,310 mg/L, reaction rate constant (K_d) = 0.1380 1/day, volatile fraction (P_v) = 0.6300, digester detention time (theta_c) = 20.0000 day, digester volume (V_d) = 13,299 m^3.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Q_{i} = 1305\ \text{m^3/day}Step 6 — Check: returning Q_i = 1,305 m^3/day to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 2,609 — kept a factor of two that cancels in the correct rearrangement.
- 652.4 — dropped that same factor in the other direction.
- 1,435 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion volatile solids reduction sizing calculation Given influent sludge flow (Q_i) = 166.0 m^3/day; influent volatile solids (X_i) = 7,690 mg/L; BOD fraction factor (F) = 0.7400; influent BOD5 (S_i) = 280.0 mg/L; digester volatile solids (X_d) = 15,310 mg/L; reaction rate constant (K_d) = 0.1510 1/day; volatile fraction (P_v) = 0.7200; digester detention time (theta_c) = 25.5000 day, determine the digester volume (V_d) in m^3.
Given
influent sludge flow (Q_i) = 166.0 m^3/day
influent volatile solids (X_i) = 7,690 mg/L
influent BOD5 (S_i) = 280.0 mg/L
Find
digester volume (V_d), in m^3
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except V_d is given, so isolate V_d symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 3 — schematic for Aerobic Digestion — solve for digester volume (case 2) — Aerobic Digestion (3)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for V_d:
Step 3 — List the givens: influent sludge flow (Q_i) = 166.0 m^3/day, influent volatile solids (X_i) = 7,690 mg/L, BOD fraction factor (F) = 0.7400, influent BOD5 (S_i) = 280.0 mg/L, digester volatile solids (X_d) = 15,310 mg/L, reaction rate constant (K_d) = 0.1510 1/day, volatile fraction (P_v) = 0.7200, digester detention time (theta_c) = 25.5000 day.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
V_{d} = 578.8\ \text{m^3}Step 6 — Check: returning V_d = 578.8 m^3 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 1,158 — kept a factor of two that cancels in the correct rearrangement.
- 289.4 — dropped that same factor in the other direction.
- 636.7 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion tank volume for waste activated sludge stabilization Given influent volatile solids (X_i) = 6,490 mg/L; BOD fraction factor (F) = 0.5300; influent BOD5 (S_i) = 2,720 mg/L; digester volatile solids (X_d) = 17,010 mg/L; reaction rate constant (K_d) = 0.1600 1/day; volatile fraction (P_v) = 0.7400; digester detention time (theta_c) = 30.5000 day; digester volume (V_d) = 18,442 m^3, determine the influent sludge flow (Q_i) in m^3/day.
Given
influent volatile solids (X_i) = 6,490 mg/L
influent BOD5 (S_i) = 2,720 mg/L
Find
influent sludge flow (Q_i), in m^3/day
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except Q_i is given, so isolate Q_i symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 4 — schematic for Aerobic Digestion — solve for influent sludge flow (case 2) — Aerobic Digestion (4)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for Q_i:
Step 3 — List the givens: influent volatile solids (X_i) = 6,490 mg/L, BOD fraction factor (F) = 0.5300, influent BOD5 (S_i) = 2,720 mg/L, digester volatile solids (X_d) = 17,010 mg/L, reaction rate constant (K_d) = 0.1600 1/day, volatile fraction (P_v) = 0.7400, digester detention time (theta_c) = 30.5000 day, digester volume (V_d) = 18,442 m^3.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Q_{i} = 5980\ \text{m^3/day}Step 6 — Check: returning Q_i = 5,980 m^3/day to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 11,959 — kept a factor of two that cancels in the correct rearrangement.
- 2,990 — dropped that same factor in the other direction.
- 6,577 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion design of a sludge digester Given influent sludge flow (Q_i) = 417.0 m^3/day; influent volatile solids (X_i) = 12,560 mg/L; BOD fraction factor (F) = 0.7700; influent BOD5 (S_i) = 310.0 mg/L; digester volatile solids (X_d) = 14,060 mg/L; reaction rate constant (K_d) = 0.1710 1/day; volatile fraction (P_v) = 0.8500; digester detention time (theta_c) = 23.0000 day, determine the digester volume (V_d) in m^3.
Given
influent sludge flow (Q_i) = 417.0 m^3/day
influent volatile solids (X_i) = 12,560 mg/L
influent BOD5 (S_i) = 310.0 mg/L
Find
digester volume (V_d), in m^3
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except V_d is given, so isolate V_d symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 5 — schematic for Aerobic Digestion — solve for digester volume (case 3) — Aerobic Digestion (5)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for V_d:
Step 3 — List the givens: influent sludge flow (Q_i) = 417.0 m^3/day, influent volatile solids (X_i) = 12,560 mg/L, BOD fraction factor (F) = 0.7700, influent BOD5 (S_i) = 310.0 mg/L, digester volatile solids (X_d) = 14,060 mg/L, reaction rate constant (K_d) = 0.1710 1/day, volatile fraction (P_v) = 0.8500, digester detention time (theta_c) = 23.0000 day.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
V_{d} = 2010\ \text{m^3}Step 6 — Check: returning V_d = 2,010 m^3 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 4,020 — kept a factor of two that cancels in the correct rearrangement.
- 1,005 — dropped that same factor in the other direction.
- 2,211 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion volatile solids reduction sizing calculation Given influent volatile solids (X_i) = 3,450 mg/L; BOD fraction factor (F) = 0.6900; influent BOD5 (S_i) = 970.0 mg/L; digester volatile solids (X_d) = 15,360 mg/L; reaction rate constant (K_d) = 0.0990 1/day; volatile fraction (P_v) = 0.7400; digester detention time (theta_c) = 36.5000 day; digester volume (V_d) = 15,919 m^3, determine the influent sludge flow (Q_i) in m^3/day.
Given
influent volatile solids (X_i) = 3,450 mg/L
influent BOD5 (S_i) = 970.0 mg/L
Find
influent sludge flow (Q_i), in m^3/day
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except Q_i is given, so isolate Q_i symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 6 — schematic for Aerobic Digestion — solve for influent sludge flow (case 3) — Aerobic Digestion (6)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for Q_i:
Step 3 — List the givens: influent volatile solids (X_i) = 3,450 mg/L, BOD fraction factor (F) = 0.6900, influent BOD5 (S_i) = 970.0 mg/L, digester volatile solids (X_d) = 15,360 mg/L, reaction rate constant (K_d) = 0.0990 1/day, volatile fraction (P_v) = 0.7400, digester detention time (theta_c) = 36.5000 day, digester volume (V_d) = 15,919 m^3.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Q_{i} = 5975\ \text{m^3/day}Step 6 — Check: returning Q_i = 5,975 m^3/day to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 11,950 — kept a factor of two that cancels in the correct rearrangement.
- 2,987 — dropped that same factor in the other direction.
- 6,572 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion tank volume for waste activated sludge stabilization Given influent sludge flow (Q_i) = 217.0 m^3/day; influent volatile solids (X_i) = 17,050 mg/L; BOD fraction factor (F) = 0.5500; influent BOD5 (S_i) = 1,540 mg/L; digester volatile solids (X_d) = 8,400 mg/L; reaction rate constant (K_d) = 0.1830 1/day; volatile fraction (P_v) = 0.6800; digester detention time (theta_c) = 26.5000 day, determine the digester volume (V_d) in m^3.
Given
influent sludge flow (Q_i) = 217.0 m^3/day
influent volatile solids (X_i) = 17,050 mg/L
influent BOD5 (S_i) = 1,540 mg/L
Find
digester volume (V_d), in m^3
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except V_d is given, so isolate V_d symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 7 — schematic for Aerobic Digestion — solve for digester volume (case 4) — Aerobic Digestion (7)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for V_d:
Step 3 — List the givens: influent sludge flow (Q_i) = 217.0 m^3/day, influent volatile solids (X_i) = 17,050 mg/L, BOD fraction factor (F) = 0.5500, influent BOD5 (S_i) = 1,540 mg/L, digester volatile solids (X_d) = 8,400 mg/L, reaction rate constant (K_d) = 0.1830 1/day, volatile fraction (P_v) = 0.6800, digester detention time (theta_c) = 26.5000 day.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
V_{d} = 2851\ \text{m^3}Step 6 — Check: returning V_d = 2,851 m^3 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 5,702 — kept a factor of two that cancels in the correct rearrangement.
- 1,425 — dropped that same factor in the other direction.
- 3,136 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion design of a sludge digester Given influent volatile solids (X_i) = 15,160 mg/L; BOD fraction factor (F) = 0.7700; influent BOD5 (S_i) = 810.0 mg/L; digester volatile solids (X_d) = 19,540 mg/L; reaction rate constant (K_d) = 0.0510 1/day; volatile fraction (P_v) = 0.7700; digester detention time (theta_c) = 32.0000 day; digester volume (V_d) = 2,358 m^3, determine the influent sludge flow (Q_i) in m^3/day.
Given
influent volatile solids (X_i) = 15,160 mg/L
influent BOD5 (S_i) = 810.0 mg/L
Find
influent sludge flow (Q_i), in m^3/day
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except Q_i is given, so isolate Q_i symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 8 — schematic for Aerobic Digestion — solve for influent sludge flow (case 4) — Aerobic Digestion (8)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for Q_i:
Step 3 — List the givens: influent volatile solids (X_i) = 15,160 mg/L, BOD fraction factor (F) = 0.7700, influent BOD5 (S_i) = 810.0 mg/L, digester volatile solids (X_d) = 19,540 mg/L, reaction rate constant (K_d) = 0.0510 1/day, volatile fraction (P_v) = 0.7700, digester detention time (theta_c) = 32.0000 day, digester volume (V_d) = 2,358 m^3.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Q_{i} = 205.9\ \text{m^3/day}Step 6 — Check: returning Q_i = 205.9 m^3/day to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 411.7 — kept a factor of two that cancels in the correct rearrangement.
- 102.9 — dropped that same factor in the other direction.
- 226.4 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion volatile solids reduction sizing calculation Given influent sludge flow (Q_i) = 403.0 m^3/day; influent volatile solids (X_i) = 3,680 mg/L; BOD fraction factor (F) = 0.7400; influent BOD5 (S_i) = 2,970 mg/L; digester volatile solids (X_d) = 17,200 mg/L; reaction rate constant (K_d) = 0.0710 1/day; volatile fraction (P_v) = 0.8300; digester detention time (theta_c) = 40.0000 day, determine the digester volume (V_d) in m^3.
Given
influent sludge flow (Q_i) = 403.0 m^3/day
influent volatile solids (X_i) = 3,680 mg/L
influent BOD5 (S_i) = 2,970 mg/L
Find
digester volume (V_d), in m^3
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except V_d is given, so isolate V_d symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 9 — schematic for Aerobic Digestion — solve for digester volume (case 5) — Aerobic Digestion (9)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for V_d:
Step 3 — List the givens: influent sludge flow (Q_i) = 403.0 m^3/day, influent volatile solids (X_i) = 3,680 mg/L, BOD fraction factor (F) = 0.7400, influent BOD5 (S_i) = 2,970 mg/L, digester volatile solids (X_d) = 17,200 mg/L, reaction rate constant (K_d) = 0.0710 1/day, volatile fraction (P_v) = 0.8300, digester detention time (theta_c) = 40.0000 day.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
V_{d} = 1641\ \text{m^3}Step 6 — Check: returning V_d = 1,641 m^3 to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 3,282 — kept a factor of two that cancels in the correct rearrangement.
- 820.4 — dropped that same factor in the other direction.
- 1,805 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion
aerobic digestion tank volume for waste activated sludge stabilization Given influent volatile solids (X_i) = 3,740 mg/L; BOD fraction factor (F) = 0.5600; influent BOD5 (S_i) = 4,460 mg/L; digester volatile solids (X_d) = 17,610 mg/L; reaction rate constant (K_d) = 0.0930 1/day; volatile fraction (P_v) = 0.6800; digester detention time (theta_c) = 16.0000 day; digester volume (V_d) = 13,099 m^3, determine the influent sludge flow (Q_i) in m^3/day.
Given
influent volatile solids (X_i) = 3,740 mg/L
influent BOD5 (S_i) = 4,460 mg/L
Find
influent sludge flow (Q_i), in m^3/day
Start with the thinking
- The governing relation printed in this handbook section is Aerobic Digestion.
- Everything except Q_i is given, so isolate Q_i symbolically first — never rearrange after the numbers are in.
- Tabulate each given with its unit and confirm the units are consistent with the relation before substituting.
- Aerobic digestion sizes the digester volume needed to stabilize waste activated sludge volatile solids.
Figure 10 — schematic for Aerobic Digestion — solve for influent sludge flow (case 5) — Aerobic Digestion (10)
Step-by-step solution
Step 1 — State the governing relation:
Step 2 — Rearrange symbolically for Q_i:
Step 3 — List the givens: influent volatile solids (X_i) = 3,740 mg/L, BOD fraction factor (F) = 0.5600, influent BOD5 (S_i) = 4,460 mg/L, digester volatile solids (X_d) = 17,610 mg/L, reaction rate constant (K_d) = 0.0930 1/day, volatile fraction (P_v) = 0.6800, digester detention time (theta_c) = 16.0000 day, digester volume (V_d) = 13,099 m^3.
Step 4 — Substitute the given values:
Step 5 — Evaluate:
Q_{i} = 4650\ \text{m^3/day}Step 6 — Check: returning Q_i = 4,650 m^3/day to
reproduces the given quantities, and both sides carry the same units.
Why the other options are there
- 9,300 — kept a factor of two that cancels in the correct rearrangement.
- 2,325 — dropped that same factor in the other direction.
- 5,115 — rounded an intermediate value before the final step.
Reference: FE Handbook — Aerobic Digestion